Alternating control box with alarm 2 Pumps – Hydropressor – ALH 200

Desde (sem IVA): 438.00

O envio apenas é disponibilizado para Portugal Continental e suas respetivas Regiões Autónomas: Açores e Madeira.

Descrição

Electric control and protection panel of electric pumps installed in pumping systems for hydropressors with 2 electric pumps.
Alternation of work regimes in electric pumps, with visual and audible alarm.
Pre-programmed water wait timer.
Reinforcement timing for support pump input.


Applications

Against lack of water.

Excessive motor consumption (thermal trigger).

Control circuit protection via circuit breaker.


Operation

After verifying the correct connection of the entire wiring, the motor circuit breakers must be adjusted according to the nominal intensity of the motors.

Check the operation of the pumps by turning the control selector to the Manual () position.

For Automatic operation, set the selector to Automatic (A).

During each actuation of the signal of the Alternation pressure switch, switch Pump 1 or Pump 2 alternately.

If during the actuation of the Alternation pressure switch, an action of the Reinforcement pressure switch appears, the second available Pump will turn on.

The Pumps turn off respectively when the Boost pressure switch signal and the Alternation pressure switch signal stop working.

When the minimum contact is switched off, the two pumps are switched off and the alarm output is switched on.

The alarm is canceled when the liquid level or pressure is reset.

Note: The images shown may not correspond completely to the product described.

Informação adicional

Peso n.d.
Dimensões (P x L x A) n.d.
Regulação térmica

1,6 – 2,5 A, 2,5 – 4,0 A, 4,0 – 6,3 A, 6,0 – 10,0 A, 9,0 – 14,0 A

Tensão

230V, 400V

Caixa em ABS cinza

260 x 370 x 125 mm with hinge and waterproof polycarbonate cover – IP65

Relé eletrónico modular

Micro controle brand, for alternating command and protection of electric pumps

Contactor e Relé Térmico

Recognized brand

Interruptor

General disconnect

Comutador 3 posições

Manual operation (MAN), automatic OFF (AUT), independently controlled on each electric pump

Ligação para comando remoto do arranque/paragem

By order of pressure switch or float

Sinalização de alimentação

Indication of the presence of power in the control circuit (White Flag)

Sinalização de eletrobomba

Individual indication of connected pump (Green Flag)

Sinalização disparo térmico

Individual indication of thermal trip (Red Flag)

Sinalização de alarme

Visual and audible alarm signal indication (Red Buzzer)

Acessórios / Outros

6 cable glands for supply and control cables